The thermal-environment characteristics of the existing forced-convection cooling system were compared with those of the convective cooling system, which combined the radiant-floor cooling system using floor-heating p...The thermal-environment characteristics of the existing forced-convection cooling system were compared with those of the convective cooling system, which combined the radiant-floor cooling system using floor-heating panel typically applied to apartments in South Korea with the forced-convection cooling system using improved fan coil unit. The subjective warm/cool-feeling responses to the combined radiant-floor and convective cooling system in the questionnaire survey conducted among the test subjects were analyzed to establish the basic data for the combined cooling system. The results show that in the thermal-equilibrium condition, the vertical air temperature difference in the model living room is larger in the forced-convection-cooling condition. Most of the subjects feel a proper warm/cool feeling on their entire body, but they feel colder on the foot and lower body in the combined-cooling condition.展开更多
Improvement of the heat transfer effect of cold side of a thermoelectric generator(TEG) is one of the approaches to enhance the performance of the TEG systems.As a new type of heat transfer media,nanofluids can enhanc...Improvement of the heat transfer effect of cold side of a thermoelectric generator(TEG) is one of the approaches to enhance the performance of the TEG systems.As a new type of heat transfer media,nanofluids can enhance the heat transfer performance of working liquid significantly.In this study,the performance of a commercial TEG with graphene-water(GW) nanofluid as coolants in a minichannel heat exchanger is investigated experimentally at low temperatures.The results show that the output power of TEG increases with the flow rate under 950 mL/min.However,the fluid flow rate has no influence on the output power of TEG with higher flow rate(larger than 950 mL/min) when the heat transfer dynamic balance state of the system is reached.The optimal concentration and flow rate of nanofluid are 0.1 wt%and 950 mL/min,respectively.At the optimal conditions,the improved voltage,output power and conversion efficiency with GW nanofluid applied in the cooling system are increased by11.29%,21.55%and 3.5%in comparison with those with only water applied,respectively.展开更多
基金Project(NRF-2013RIA2A1A01014020)supported by the National Research Foundation of Korea
文摘The thermal-environment characteristics of the existing forced-convection cooling system were compared with those of the convective cooling system, which combined the radiant-floor cooling system using floor-heating panel typically applied to apartments in South Korea with the forced-convection cooling system using improved fan coil unit. The subjective warm/cool-feeling responses to the combined radiant-floor and convective cooling system in the questionnaire survey conducted among the test subjects were analyzed to establish the basic data for the combined cooling system. The results show that in the thermal-equilibrium condition, the vertical air temperature difference in the model living room is larger in the forced-convection-cooling condition. Most of the subjects feel a proper warm/cool feeling on their entire body, but they feel colder on the foot and lower body in the combined-cooling condition.
基金supported by the National Natural Science Foundation of China(Grant Nos.51590902&51476095)the Natural Science Foundation of Shanghai(Grant No.14ZR1417000)+1 种基金the Key Subject of Shanghai Polytechnic University(Material Science and Engineering,Grant No.XXKZD1601)the Program for Professor of Special Appointment(Young Eastern Scholar,Grant No.QD2015052)at Shanghai Institutions of Higher Learning
文摘Improvement of the heat transfer effect of cold side of a thermoelectric generator(TEG) is one of the approaches to enhance the performance of the TEG systems.As a new type of heat transfer media,nanofluids can enhance the heat transfer performance of working liquid significantly.In this study,the performance of a commercial TEG with graphene-water(GW) nanofluid as coolants in a minichannel heat exchanger is investigated experimentally at low temperatures.The results show that the output power of TEG increases with the flow rate under 950 mL/min.However,the fluid flow rate has no influence on the output power of TEG with higher flow rate(larger than 950 mL/min) when the heat transfer dynamic balance state of the system is reached.The optimal concentration and flow rate of nanofluid are 0.1 wt%and 950 mL/min,respectively.At the optimal conditions,the improved voltage,output power and conversion efficiency with GW nanofluid applied in the cooling system are increased by11.29%,21.55%and 3.5%in comparison with those with only water applied,respectively.