Automatic Voltage Regulator Test of Three Gorges Right Bank Hydropower Station 被引量:1
1
作者 Wu Tao Zhou Ji +5 位作者 Pu Jun Su Weimin Xie Huan Huo Chengxiang Deng Xiaojun Yao Qian 《Electricity》 2012年第3期24-29,共6页
Based on real-time digital simulations(RTDS),a laboratory environment similar to the real-time operation situation of the Three Gorges Hydropower Station is established.Then,the causes for the power fluctuation of the... Based on real-time digital simulations(RTDS),a laboratory environment similar to the real-time operation situation of the Three Gorges Hydropower Station is established.Then,the causes for the power fluctuation of the second generator by errors in the rotor rotating speed calculation are found,and the tuning method of the speed related parameters are given.The damping and reverse tuning characteristics of power system stabilizers(PSSs)in the digital automatic voltage regulator(AVR)are compared and investigated in the frequency range of 0.18-1.1 Hz.The efficiency of the proposed tuning method for ensuring power system stability is verified by RTDS.Finally,field tests show the validity of the laboratory test results. 展开更多
关键词 power system stabilizers (PSS) angular speed oscillating reactance real-time digital simulation rtds
下载PDF
RTDS hardware implementation and simulation of SHAF for mitigation of harmonics using p-q control strategy with PI and fuzzy logic controllers
2
作者 Suresh MIKKILI A. K. PANDA 《Frontiers of Electrical and Electronic Engineering in China》 CSCD 2012年第4期427-437,共11页
The main objective of this paper is to develop PI and fuzzy controllers to analyze the performance of instantaneous real active and reactive power (p-q) control strategy for extracting reference currents of shunt ac... The main objective of this paper is to develop PI and fuzzy controllers to analyze the performance of instantaneous real active and reactive power (p-q) control strategy for extracting reference currents of shunt active filters (SHAFs) under balanced, unbalanced, and balanced non-sinusoidal conditions. When the supply voltages are balanced and sinusoidal, both controllers converge to the same compensation characteristics. However, if the supply voltages are distorted and/or unbalanced sinusoidal, these controllers result in different degrees of compensation in harmonics. The p-q control strategy with PI controller is unable to yield an adequate solution when source voltages are not ideal. Extensive simulations were carried out with balance, unbalanced, and non-sinusoidal conditions. Simulation results validate the superiority of fuzzy logic controller over PI controller. The three-phase four-wire SHAF system is also implemented on a real-time digital simulator (RTDS hardware) to further verify its effective-ness. The detailed simulation and RTDS hardware results are included. 展开更多
关键词 harmonic compensation shunt active filter(SHAF) p-q control strategy PI controller fuzzy logiccontroller real-time digital simulator rtds hardware)
原文传递
Modeling methodology and fault simulation of distribution networks integrated with inverter-based DG 被引量:8
3
作者 Longchang Wang Houlei Gao Guibin Zou 《Protection and Control of Modern Power Systems》 2017年第1期370-378,共9页
The increasing penetration of inverter-based distributed generations(DGs)significantly affects the fault characteristics of distribution networks.Fault analysis is a keystone for suitable protection scheme design.This... The increasing penetration of inverter-based distributed generations(DGs)significantly affects the fault characteristics of distribution networks.Fault analysis is a keystone for suitable protection scheme design.This paper presents the modelling methodology for distribution networks with inverter-based DGs and performs fault simulation based on the model.Firstly,a single inverter-based DG model based on the cascaded control structure is developed.Secondly,a simulation model of distribution network with two inverter-based DGs is established.Then,different fault simulations are performed based on the Real Time Digital Simulator(RTDS).Theoretical analyses are conducted to justify the simulation results,including the equivalent circuit of distribution networks with inverter-based DGs and the solution method for loop currents. 展开更多
关键词 Distribution network Inverter-based distributed generation(DG) simulation model Fault analysis Real time digital Simulator(rtds)