Comparison between open phase fault of arc suppression coil and single phase to earth fault in coal mine distribution network 被引量:3
1
作者 LI Xiao-bo WANG Chong-lin 《Journal of China University of Mining and Technology》 EI 2008年第3期368-372,共5页
When, in a coal mine distribution network whose neutral point is grounded by an arc suppression coil (ASC), a fault occurs in the ASC, compensation cannot be properly realized. Furthermore, it can damage the safe and ... When, in a coal mine distribution network whose neutral point is grounded by an arc suppression coil (ASC), a fault occurs in the ASC, compensation cannot be properly realized. Furthermore, it can damage the safe and reliable run of the network. We first introduce a three-phase five-column arc suppression coil (TPFCASC) and discuss its autotracking compensation theory. Then we compare the single phase to ground fault of the coal mine distribution network with an open phase fault at the TPFCASC using the Thévenin theory, the symmetrical-component method and the complex sequence network respectively. The results show that, in both types of faults, zero-sequence voltage of the network will appear and the maximum magnitude of this zero-sequence voltage is different in both faults. Based on this situation, a protection for the open phase fault at the TPFCASC should be estab-lished. 展开更多
关键词 open phase PROTECTION single phase to ground fault three-phase five-column arc suppression coil (TPFCASC)
下载PDF
Application of DC component to select fault branch in arc suppression coil grounding system 被引量:2
2
作者 Zhi-Jie WANG Yan-Wen WANG 《Journal of Coal Science & Engineering(China)》 2013年第3期396-401,共6页
When single phase earth fault occurs in the arc suppression coil grounding system, the amplitude of the transient capacitance current is high and decays fast, but the attenuation of the transient inductance current is... When single phase earth fault occurs in the arc suppression coil grounding system, the amplitude of the transient capacitance current is high and decays fast, but the attenuation of the transient inductance current is much slower. This paper analyses the DC component of fault branch, and has found it is much bigger than that of the normal branches in transient state. All the simulation results obtained from three compensation types, different fault time and different wave cycles show that the DC component of fault branch is much higher than that of those normal branches. These results verify the effectiveness of taking the DC component as the method of fault line selection in the arc suppression coil grounding system. 展开更多
关键词 DC component arc suppression coil fault line selection transient state
下载PDF
可抑制故障电流中谐波分量的新型消弧线圈设计
3
作者 梁定守 陈坤燚 +1 位作者 胡庆威 柯贤旺 《湖北民族大学学报(自然科学版)》 CAS 2024年第3期375-381,394,共8页
针对当前的有源消弧方法因谐波电流检测精度不足而效果较差,以及传统消弧线圈在谐波影响下容易导致消弧失败的问题,设计了一种无须谐波检测便可有效抑制故障点残流中谐波分量的新型消弧线圈。该消弧线圈由逆变器并联传统消弧线圈构成,... 针对当前的有源消弧方法因谐波电流检测精度不足而效果较差,以及传统消弧线圈在谐波影响下容易导致消弧失败的问题,设计了一种无须谐波检测便可有效抑制故障点残流中谐波分量的新型消弧线圈。该消弧线圈由逆变器并联传统消弧线圈构成,其中逆变器的指令电压根据中性点电位进行调整,可使逆变器支路不产生基波电流;逆变器的低谐波阻抗特性可有效降低故障点残流中的谐波分量;同时传统消弧线圈过补偿可抵消电容电流。经过Matlab和PSCAD/EMTDC(power systems computer aided design/electromagnetic transients including direct current)仿真,结果显示新型消弧线圈将故障点处的5次谐波、7次谐波分别由25.62、65.85 A降低到了0.11、0.57 A,能够实现可靠消弧。该研究在配电网消弧领域具有一定的应用前景。 展开更多
关键词 谐波电流 消弧线圈 故障点残流 逆变器 低谐波阻抗 过补偿
下载PDF
顺北油田二区变电站35kV电压互感器烧毁故障分析
4
作者 魏斌 蒲军 《电气技术》 2024年第2期74-78,共5页
油田电网运行中,35kV系统和10kV系统为中性点经消弧线圈接地系统或不接地系统,在电网发展时期,系统参数可能处于谐振区,电磁式电压互感器易发生铁磁谐振现象,产生过电压或过电流,严重时会烧毁电压互感器。本文对顺北油田二区变电站35kV... 油田电网运行中,35kV系统和10kV系统为中性点经消弧线圈接地系统或不接地系统,在电网发展时期,系统参数可能处于谐振区,电磁式电压互感器易发生铁磁谐振现象,产生过电压或过电流,严重时会烧毁电压互感器。本文对顺北油田二区变电站35kV系统发生的3次电压互感器烧毁故障开展研究,得出电力系统处于谐振区,电压互感器铁磁谐振是造成电压互感器烧毁的原因。通过采取投入消弧线圈、应用饱和特性好的电压互感器和4PT改造等措施,有效治理了铁磁谐振。 展开更多
关键词 铁磁谐振 消弧线圈 励磁特性
下载PDF
基于自耦变压器结构的双调节式矿用消弧线圈研究
5
作者 王曦 《科技创新与应用》 2024年第34期118-123,共6页
该文设计一种带有三次绕组的自耦变压器结构矿用消弧线圈,二次绕组接晶闸管投切电容电路,第三绕组具有高短路阻抗特性,输出端接反并联晶闸管,对消弧线圈进行细调。通过系统双调节回路的协调控制,可实现变压器消弧线圈的大范围连续调节... 该文设计一种带有三次绕组的自耦变压器结构矿用消弧线圈,二次绕组接晶闸管投切电容电路,第三绕组具有高短路阻抗特性,输出端接反并联晶闸管,对消弧线圈进行细调。通过系统双调节回路的协调控制,可实现变压器消弧线圈的大范围连续调节。对消弧线圈的运行参数、控制策略以及调谐方法进行深入的研究分析。这种消弧线圈具有响应速度快、连续调节范围宽、谐波小、伏安特性好及补偿精度高等优点。MATLAB仿真验证新型矿用消弧线圈的合理性和优越性。 展开更多
关键词 配电网 单相接地故障 消弧线圈 晶闸管投切电容 可控电抗
下载PDF
某酒厂新污水处理厂沼气发电项目电气设计
6
作者 罗兵 刘莉萍 +1 位作者 王伟 费文伟 《机电工程技术》 2024年第6期277-281,共5页
通过对沼气发电技术进行分析,研究了沼气发电项目中的电气设计要点问题。首先以某酒厂新污水处理厂沼气发电项目为例进行分析,对电气主接线设计要点进行了探讨,研究了设置消弧线圈的必要性,分析了该地安装消弧线圈存在的协同工作问题,... 通过对沼气发电技术进行分析,研究了沼气发电项目中的电气设计要点问题。首先以某酒厂新污水处理厂沼气发电项目为例进行分析,对电气主接线设计要点进行了探讨,研究了设置消弧线圈的必要性,分析了该地安装消弧线圈存在的协同工作问题,并给出了解决办法。此外,详细研究了沼气发电项目系统设计中的关键环节,对该项目的发电机主保护、变压器主保护、线路主保护等进行了系统设计,并且设计了计算机监控系统,以便实时监测发电设备的状态、性能参数等信息,及时识别和处置异常情况。研究成果不仅为该项目的优化提供了有效建议,同时也为其他类似工程在电气设计方面提供了有益的参考和指导。 展开更多
关键词 污水处理 沼气发电 消弧线圈 电气设计
下载PDF
消弧线圈有载开关误动调挡原因分析及解决措施
7
作者 何聪 胡柏玮 +2 位作者 古丝月 杜南希 肖翔宇 《重庆电力高等专科学校学报》 2024年第4期1-6,共6页
对可能引起消弧线圈有载开关误动调挡的原因进行分析,指出消弧线圈内铁铬铝阻尼电阻偏差大和调挡控制器闭锁程序缺陷是导致有载开关误动调挡的主要原因。提出用镍铬阻尼电阻替代铁铬铝阻尼电阻,并在有载开关调挡电机电源回路中增加电压... 对可能引起消弧线圈有载开关误动调挡的原因进行分析,指出消弧线圈内铁铬铝阻尼电阻偏差大和调挡控制器闭锁程序缺陷是导致有载开关误动调挡的主要原因。提出用镍铬阻尼电阻替代铁铬铝阻尼电阻,并在有载开关调挡电机电源回路中增加电压闭锁模块,来有效解决消弧线圈有载开关误动调挡问题。将上述两条措施应用至重庆市某电力公司辖区变电站内116套消弧线圈成套装置中,运行结果表明,这两条措施确能有效避免消弧线圈有载开关误动调挡,能进一步提高电网供电可靠性。 展开更多
关键词 消弧线圈 有载开关 调挡装置 阻尼电阻 电气闭锁
下载PDF
一种典型10 kV电缆线路接地故障快速隔离动作分析
8
作者 张启亮 刘倩影 《黑龙江电力》 CAS 2024年第3期196-201,共6页
针对一起变电站中性点接地方式改造过程中零序跳闸事件,提出10 kV电缆线路的典型拓扑结构。结合实际工作,阐述当前试点应用中的经消弧线圈并联小电阻接地方式,并给出零序保护定值推荐值。结合案例,全面分析接地变跳闸逻辑错误、电缆线... 针对一起变电站中性点接地方式改造过程中零序跳闸事件,提出10 kV电缆线路的典型拓扑结构。结合实际工作,阐述当前试点应用中的经消弧线圈并联小电阻接地方式,并给出零序保护定值推荐值。结合案例,全面分析接地变跳闸逻辑错误、电缆线路FA自愈失败等故障原因,并提出改进措施。 展开更多
关键词 消弧线圈 低电阻 单相接地故障
下载PDF
10 kV中性点接地方式由消弧线圈变为小电阻的改造方法及常见问题探讨
9
作者 刘议华 邱爽 +1 位作者 薛思祥 阎鼎 《农村电气化》 2024年第2期26-29,共4页
随着城市电网的发展,电缆在10 kV配网中的比重不断增加,消弧线圈接地方式的各种弊端不断凸显,小电阻接地方式的优势则越发明显。介绍了10 kV城市配电网中性点接地方式由消弧线圈改造为小电阻的总体思路及流程,并对小电阻接地方式存在的... 随着城市电网的发展,电缆在10 kV配网中的比重不断增加,消弧线圈接地方式的各种弊端不断凸显,小电阻接地方式的优势则越发明显。介绍了10 kV城市配电网中性点接地方式由消弧线圈改造为小电阻的总体思路及流程,并对小电阻接地方式存在的一系列问题进行了探讨。 展开更多
关键词 配电网络 消弧线圈接地 小电阻接地
下载PDF
一例单相接地故障管理系统并联运行下的误判案例分析
10
作者 邓军 周强 《农村电气化》 2024年第10期58-61,共4页
对某化工企业10 kV电力系统发生单相接地故障时,2套MXJD单相接地故障管理系统在并联运行下的误判进行了研究。通过对该案例的现象、原因、影响和处理过程探讨,剖析MXJD单相接地故障管理系统的工作原理、系统设计、数据共享等关键参数,... 对某化工企业10 kV电力系统发生单相接地故障时,2套MXJD单相接地故障管理系统在并联运行下的误判进行了研究。通过对该案例的现象、原因、影响和处理过程探讨,剖析MXJD单相接地故障管理系统的工作原理、系统设计、数据共享等关键参数,提出了单相接地故障管理系统在并联运行时的一些建议,为电网可靠运行提供参考。 展开更多
关键词 单相接地故障 并联运行 消弧线圈 数据共享
下载PDF
The Research on Neutral Grounding Scheme of Fengxian 35kV and 10 kV Power Grid 被引量:1
11
作者 Siming Hua Hua Zhang +2 位作者 Feng Qian Chunjie Chen Meixia Zhang 《Energy and Power Engineering》 2013年第4期897-901,共5页
Combined with actual situation of Fengxian power Supply Company, the neutral grounding modes of Fengxian 35 kV and 10 kV power grid are studied in the paper. The different frequencies injected method is used to measur... Combined with actual situation of Fengxian power Supply Company, the neutral grounding modes of Fengxian 35 kV and 10 kV power grid are studied in the paper. The different frequencies injected method is used to measure the capacitive current of Fengxian 28 substations, and the neutral grounding modes of the 28 substations are determined based on the measured values of capacitive current. 展开更多
关键词 NEUTRAL GROUNDING Mode Different Frequency Injected Method Capacitive Current arc suppression coil Low Resistance
下载PDF
基于模型预测控制的配电网单相接地故障有源消弧 被引量:5
12
作者 常新建 邵文权 +1 位作者 程远 卫晓辉 《电力工程技术》 北大核心 2023年第2期161-169,共9页
针对配电网非有效接地系统中单相接地故障消弧的难题,现多采用附加有源补偿和消弧线圈相结合的方案对接地故障电弧进行抑制,而有源补偿系统控制策略的性能直接决定了消弧性能。文中设计了基于模型预测控制(model predictive control,MPC... 针对配电网非有效接地系统中单相接地故障消弧的难题,现多采用附加有源补偿和消弧线圈相结合的方案对接地故障电弧进行抑制,而有源补偿系统控制策略的性能直接决定了消弧性能。文中设计了基于模型预测控制(model predictive control,MPC)的有源消弧实现方案,首先分析采用注入电流方式的有源消弧原理,然后采用三级联H桥多电平逆变器作为有源消弧系统主拓扑,优选代价函数,设计基于MPC的有源消弧闭环控制系统。该控制系统相较基于比例积分(proportional integral,PI)控制的有源消弧闭环控制系统,无须进行参数整定即可实现对多次谐波电流的精确追踪,进而有效补偿接地电流。仿真及实验结果均表明:文中所提方案能更加有效地抑制接地故障电流,满足不同场景可靠消弧的要求。 展开更多
关键词 级联H桥 单相接地故障 消弧线圈 模型预测控制(MPC) 电流注入 有源消弧
下载PDF
预防电缆沟起火的小电流接地系统单相接地故障处理 被引量:15
13
作者 刘健 张薛鸿 +4 位作者 张小庆 张志华 徐丙垠 徐阳 李瑞桂 《电力系统保护与控制》 EI CSCD 北大核心 2023年第6期21-29,共9页
为避免小电流接地系统单相接地故障引发的电缆沟起火事故,采用火灾动态仿真分析方法得到了接地故障电弧导致电缆沟引燃的时间与空间阈值。在此基础上阐述了预防电缆沟起火的综合治理措施。论述了兼具相控消弧线圈和预调式消弧线圈优点... 为避免小电流接地系统单相接地故障引发的电缆沟起火事故,采用火灾动态仿真分析方法得到了接地故障电弧导致电缆沟引燃的时间与空间阈值。在此基础上阐述了预防电缆沟起火的综合治理措施。论述了兼具相控消弧线圈和预调式消弧线圈优点的相控预调式消弧线圈的实现方式及其实验测试数据。阐述了跨线相继接地故障的处理方法,包含以暂态量法为主的连续检测过程及以稳态量法为主的增补处理过程。给出了单相接地保护跳闸延时的整定依据及间断性接地故障的处理方法。针对城区和郊区配电线路分别论述了集中智能容错单相接地故障处理方法和基于合闸速断的分布智能单相接地故障处理方法。介绍了在陕西全省172座110 kV变电站供电区域范围内配电网的整体应用成效,表明所论述的技术措施的有效性。 展开更多
关键词 电缆沟起火 小电流接地系统 单相接地 消弧线圈 继电保护 馈线自动化
下载PDF
谐振接地系统对地电容与消弧线圈电感统一测量方法 被引量:1
14
作者 谢大为 王京景 +2 位作者 朱争高 丁超 李生虎 《电子测量技术》 北大核心 2023年第18期23-28,共6页
配电网对地电容的准确测量有助于保证消弧线圈的补偿效果,降低故障对配电网的损害。提出一种基于信号注入法与快速傅里叶变换的谐振接地系统对地电容与消弧线圈电感统一测量方法。首先建立中性点电压与系统对地电容、消弧线圈电感关系... 配电网对地电容的准确测量有助于保证消弧线圈的补偿效果,降低故障对配电网的损害。提出一种基于信号注入法与快速傅里叶变换的谐振接地系统对地电容与消弧线圈电感统一测量方法。首先建立中性点电压与系统对地电容、消弧线圈电感关系。其次向中性点接入非工频电流源,利用快速傅里叶变换得到中性点电压关于电流源频率分量,消除工频误差。然后根据等效电路实现系统对地电容与消弧线圈电感的统一测量。最后通过Simulink搭建仿真模型进行分析。结果表明,该方法适用于消弧线圈直接接地、消弧线圈并联电阻接地和串联电阻接地运行方式。三相不对称条件下,对地电容与消弧线圈电感最大误差分别为0.11%和0.1%;三相对称条件下,最大误差分别为1.3%和1.8%。 展开更多
关键词 配电网 参数测量 对地电容 消弧线圈 信号注入法 快速傅里叶变换
原文传递
基于动态接地方式的配电网单相接地故障区域隔离 被引量:2
15
作者 邓晓风 李景禄 +1 位作者 徐雄军 伊国强 《电气自动化》 2023年第1期59-61,共3页
中性点经消弧线圈接地配电网发生单相接地故障时,受消弧线圈调谐与过渡电阻的影响,导致故障选线和隔离困难,严重影响了人身安全与供电可靠性。为此,提出了一种基于动态接地方式的故障区域隔离方案,将消弧线圈接地改造为动态接地,对动态... 中性点经消弧线圈接地配电网发生单相接地故障时,受消弧线圈调谐与过渡电阻的影响,导致故障选线和隔离困难,严重影响了人身安全与供电可靠性。为此,提出了一种基于动态接地方式的故障区域隔离方案,将消弧线圈接地改造为动态接地,对动态切换前后的各配电终端零序电流变化规律进行了理论分析,并提出节点零序电流比较法进行故障区段定位。现场试验验证了方案的准确性与可靠性,实现了0~4000Ω高阻接地故障下的区域隔离,为解决消弧线圈接地方式下的故障区段定位难题提供了工程应用案例。 展开更多
关键词 消弧线圈接地 动态接地 节点零序电流比较法 高阻接地 故障区域隔离
下载PDF
基于零序导纳的消弧线圈接地系统馈线单相断线故障保护方法 被引量:6
16
作者 霍建彬 李巍 +3 位作者 周歧林 白浩 李党 袁智勇 《南方电网技术》 CSCD 北大核心 2023年第5期117-124,共8页
配电网规模逐渐扩大且运行环境复杂多变,消弧线圈接地系统的单相断线故障愈发频繁,由于消弧线圈的补偿作用,发生断线故障时的电气量较弱,难以监测故障构建保护方案。针对消弧线圈系统馈线发生单相断线故障,提出了一种基于零序导纳的消... 配电网规模逐渐扩大且运行环境复杂多变,消弧线圈接地系统的单相断线故障愈发频繁,由于消弧线圈的补偿作用,发生断线故障时的电气量较弱,难以监测故障构建保护方案。针对消弧线圈系统馈线发生单相断线故障,提出了一种基于零序导纳的消弧线圈接地系统馈线单相断故障保护方法。首先分析线路首端零序电流和母线零序电压的特征,利用零序电流与零序电压之比得到零序导纳,指出非故障线路零序导纳相位在第一象限,而故障线路零序导纳相位在第二象限或第三象限。然后对消弧线圈过补偿情况的故障线路零序导纳进行改进,用线路零序导纳相位乘以对应的符号系数,扩大了故障线路与非故障线路零序导纳相位对的差异,基于零序导纳的相位特性建立了故障保护判据。最后通过PSCAD/EMTDC仿真,结果验证了所提方法的可靠性。 展开更多
关键词 消弧线圈接地系统 单相断线故障 零序导纳 断线保护
下载PDF
影响单相接地故障选线准确性的主要因素研究 被引量:4
17
作者 牛成林 李洋 +4 位作者 王亮 薛倩楠 李瑞祥 辛小娟 周立华 《电力电容器与无功补偿》 2023年第4期34-40,共7页
随着中国配电网的发展,配电网系统容量的增长越来越受到消弧线圈容量的限制,但与此同时选线装置准确率的不够,使得配电网又无法摆脱消弧线圈容量的束缚。因而为提升选线装置的准确率,利用了Matlab/Simulink软件,对中性点不接地和经消弧... 随着中国配电网的发展,配电网系统容量的增长越来越受到消弧线圈容量的限制,但与此同时选线装置准确率的不够,使得配电网又无法摆脱消弧线圈容量的束缚。因而为提升选线装置的准确率,利用了Matlab/Simulink软件,对中性点不接地和经消弧线圈接地系统发生单相接地故障时的主要稳态特征在工频条件下进行了仿真分析,进而探究了系统不接地和经消弧线圈以及中性点并联选线中电阻对稳态幅值法单相接地故障选线的影响。基于仿真结果表明,在故障过渡电阻阻值位于约1000Ω以下的情况下,在中性点不接地系统中该方法的选线效果最好,但在经消弧线圈接地系统中中性点并联选线中电阻也可以对该方法在经消弧线圈接地系统中的选线效果有较大提升;而在故障过渡电阻阻值位于约1000Ω以上的情况下,不论系统是否经消弧线圈接地和投入中性点选线中值电阻该方法均缺乏良好效果,需要应用其它新方法。 展开更多
关键词 消弧线圈 中性点中值电阻 单相接地故障
下载PDF
小电流接地系统单相接地故障快速处置改造 被引量:1
18
作者 刘小亮 朱浩男 艾先政 《电工技术》 2023年第S01期91-92,95,共3页
采用小电流接地方式的城市配电网发生单相接地故障时应快速隔离故障。从现场排查、技术路线选择、小电流接地选线装置、现场试验四个方面介绍了单相接地故障快速处置改造工作的重点。
关键词 小电流接地 单相接地 消弧线圈 选线装置
下载PDF
基于稳态零序电流分布的单相接地故障区间定位技术研究 被引量:1
19
作者 苏添易 《电工技术》 2023年第13期103-105,共3页
针对单相接地故障检测中的故障区间定位问题,提出一种基于稳态零序电流分布的单相接地故障区间定位技术。通过详细分析发生单相接地故障前后稳态零序电流的分布特性,得出基于稳态零序电流特征的故障判据,并基于故障判据给出详细判断流... 针对单相接地故障检测中的故障区间定位问题,提出一种基于稳态零序电流分布的单相接地故障区间定位技术。通过详细分析发生单相接地故障前后稳态零序电流的分布特性,得出基于稳态零序电流特征的故障判据,并基于故障判据给出详细判断流程。该定位技术可有效补充现有方法的不足,在不增加费用的基础上,细化故障区间,进一步缩短故障排查时间。 展开更多
关键词 单相接地故障 稳态零序电流 消弧线圈接地
下载PDF
基于零序电流直流分量比的单相接地保护研究
20
作者 张敏 周暄 《煤炭工程》 北大核心 2023年第S01期95-99,共5页
针对高压供电系统中小电流故障选线方法在实际应用中使用效果不佳的问题,以尔林兔35 kV箱变的实际参数为例,以理论分析和计算机仿真相结合的方法,研究其10 kV系统消弧线圈接地方式下发生单相漏电故障的暂态分析,得到故障选线判据。首先... 针对高压供电系统中小电流故障选线方法在实际应用中使用效果不佳的问题,以尔林兔35 kV箱变的实际参数为例,以理论分析和计算机仿真相结合的方法,研究其10 kV系统消弧线圈接地方式下发生单相漏电故障的暂态分析,得到故障选线判据。首先通过列解等效电路的微分方程,得出了非故障线路零序电流和故障线路零序电流的计算公式,并采用MATLAB脚本程序进行编程验证;然后详细描述了各电气量与接地电阻的关系,指出接地故障瞬间故障相电压初始相位是影响暂态过程的重要因素;再利用傅里叶变换和傅氏算法分别给出直流分量的计算方法,并用实际参数进行了相互验证。最后进行了MATLAB/SIMULINK仿真,验证了等效电路和理论分析的正确性以及故障选线判据的选线准确性和普适性。 展开更多
关键词 故障选线 消弧线圈 单相接地 漏电保护 直流分量比
下载PDF